Section AG106 Entrapment Protection for Swimming Pool and Spa Suction Outlets

AG106.1 General. Suction outlets shall be designed to produce circulation throughout the pool or spa. Single outlet systems, such as automatic vacuum cleaner systems, or other such multiple suction outlets whether isolated by valves or otherwise shall be protected against user entrapment.

1. All Pool and Spa suction outlets shall be provided with a cover that conforms with ANSI/ASME A112.19.8M, or a 12 ² × 12 ² drain grate or larger, or an approved channel drain system.

Exception: Surface skimmers

AG106.3 Atmospheric vacuum relief system required. All pool and spa single or multiple outlet circulation systems shall be equipped with atmospheric vacuum relief should grate covers located therein become missing or broken. Such vacuum relief systems shall include at least one approved or engineered method of the type specified herein, as follows:

1.  Safety vacuum release system conforming to ASME A112.19.17, or

2. An approved gravity drainage system

AG106.4 Dual drain separation. Single or multiple pump circulation systems shall be provided with a minimum of two (2) suction outlets of the approved type. A minimum horizontal or vertical distance of three (3) feet shall separate such outlets. These suction outlets shall be piped so that water is drawn through them simultaneously through a vacuum relief-protected line to the pump or pumps.

AG106.5 Pool cleaner fittings. Where provided, vacuum or pressure cleaner fitting(s) shall be located in an accessible position(s) at least (6) inches and not greater than twelve (12) inches below the minimum operational water level or as an attachment to the skimmer(s).

http://www.cpsc.gov/pssa.pdf

http://www.dos.state.ny.us/CODE/pools.htm

From:  http://www.vac-alert.com/building_health.html

http://www.vac-alert.com/documents/allinclusive.pdf

Building/Planning/Permits


The Vac-Alert VA2000 is listed (014545) with Applied Research Laboratories (ARL) and met or exceeded the ASME/ANSI 112.19.17 Manufactured Safety Vacuum Release System (SVRS) for residential commercial swimming pool, spa, hot tub, and wading pool suction systems.

Dual Drain and Vent Pipe Limitations

ASME/ANSI Report

UL Test Results

IAPMO Test Results


Vac-Alert's VA-2000 complies with ASME/ANSI A112.19.17 as required by the International Building Codes (IBC) and the International Residential Codes (IRC)

The International Code Council's International Building Codes and International Residential Codes, as well as the Consumer Product Safety Commission's Guidelines, include language on the use of Safety Vacuum Release Systems. 

The American National Standards Institute (ANSI) is an agency that "accredits" standards promulgators such as ASME, ASTM & NSPI. This is the national system for insuring that standards development organizations follow strict procedures and maintain a true consensus process. 

International Code Council (ICC) - The ICC was established in 1994 as a non profit organization dedicated to the development of a single set of comprehensively nationally recognized construction codes. 

The International Building Code (IBC) and the International Residential Code (IRC) both mandate "three layers of protection." IBC 3109.5 and IRC AG 106 require all pools and spas (regardless of water depth) to be equipped with an accepted method for vacuum relief. These codes call for devises that meet ASME A112.19.17 standards to provide this vacuum relief. The vast majority of state and local governments utilize the IBC and the IRC codes as models for their own codes. 

Consumer Product Safety Commission (CPSC) - The CPSC published Guidelines for Entrapment Hazards: Making Pools and Spas Safer in March 2005. Included in the recommendations is the use of SVRSs for newly constructed pools and existing pools…………… 

"Due to care and maintenance concerns associated with circulation systems that include suction outlets (main drains) and covers, consideration should be given to the installation of a back-up systems that relieves entrapping suction and/or shuts down the pump when a blockage is detected [ e.g., an SVRS]………" 


TEMPERATURE WARNING ON THE VA2000

The Model VA-2000 meets or exceeds the -40F to 140F temperature performance testing set by the ASME/ANSI A112.19.17 Standard for Manufacturing. 

Safety Vacuum Release Systems. We strongly suggest that the VA2000 not be left in below freezing temperatures where the circulation system is not continually running or not protected by a pump house. In such cases, condensation could freeze piping and ice may impair or disable the safety features of the VA-2000. For installations that require winterization, the Model VA-2000 should be removed and stored , and then re-installed upon system start-up.